SCB10 Series Resin Insulated Dry-Type Transformer

2026-02-11

Features


● Safe, flame-retardant, fireproof, pollution-free, and can be directly installed at the load center.


● Maintenance-free, easy to install, and low overall operating cost.


● Excellent moisture resistance; can operate normally at 100% humidity and can be put back into operation without pre-drying after shutdown.


● Low loss, low partial discharge, low noise, strong heat dissipation; can operate at 150% rated load under forced air cooling.


● Equipped with a complete temperature protection and control system, providing reliable protection for the safe operation of the transformer.


● High reliability. Research on products already in operation shows that reliability indicators have reached international advanced levels.


Structural Features


Foil Coil: The low-voltage winding uses a single section of copper foil, along with F-class turn insulation, wound on a dedicated low-voltage foil winding machine. The foil coil effectively solves the prominent problems of high short-circuit stress, ampere-turn imbalance, poor heat dissipation, and unstable winding helix angle and manual welding quality in low-voltage, high-current coil windings. Simultaneously, our company uses resin potting and curing at the winding ends for moisture and contamination prevention. The copper busbars are automatically welded using argon arc welding.


Temperature control device: The transformer uses a BWDK series signal thermometer. The temperature sensing element is embedded in the upper half of the low-voltage coil, which can automatically detect and cyclically display the operating temperature of each phase coil, and has over-temperature alarm and tripping functions.


Model and Meaning


SC(B)10 Series Resin Insulated Dry-Type Transformer


Rated Capacity (KVA) Voltage Combination Connection Group Number No-load Loss (W) Load Loss (W) No-load Current (%) Short-circuit Impedance (%)

High Voltage


(KV) High Voltage Tap Range Low Voltage (KV) 130℃(B) (100℃) 155℃(F) (120℃) 180℃(H) (145℃)


30 6


6.3


6.6


10

10.5


11 ±2.5%


±5% 0.4 Dyn11


Yyn0 190 670 710 760 2.0 4.0


50 270 940 1000 1070 2.0


80 370 1290 1380 1480 1.5

100 400 1480 1570 1690 1.5

125 470 1740 1850 1980 1.3

160 540 2000 2130 2280 1.3

200 ±2X2.5%

±5% 620 2370 2530 2710 1.1

250 720 2590 2760 2960 1.1

315 880 3270 3470 3730 1.0

400 980 3750 3990 4280 1.0

500 1150 4590 4880 5230 1.0

630 1340 5530 5880 6290 0.85


630 1300 5610 5960 6400 0.85 6.0


800 1520 6550 6960 7460 0.85


1000 1770 7650 8130 8760 0.85


1250 2090 9100 9690 10300 0.85


1600 2450 11000 11700 12500 0.85


2000 3050 13600 14400 15500 0.70


2500 3600 16100 17100 18400 0.70


1600 2450 1220 12900 13900 0.85 8.0


2000 3050 15000 15900 17100 0.70


2500 3600 17700 18800 20200 0.70

Rated Capacity (KVA)

Voltage Combination

Connection Group Number

No-load Loss (W)

Load Loss (W)

No-load Current (%)

Short-circuit Impedance (%)

High Voltage


(KV)

High Voltage Tap Range

Low Voltage (KV)


130℃ (B) (100℃)


155℃ (F) (120℃)


180℃ (H) (145℃)

30

6

6.3

6.6

10

10.5

11

±2.5%

±5%

0.4

Dyn11

Yyn0

190

670

710

760

2.0

4.0

50

270

940

1000

1070

2.0

80

370

1290

1380

1480

1.5

100

400

1480

1570

1690

1.5

125

470

1740

1850

1980

1.3

160

540

2000

213 0

2280

1.3

200

±2X2.5%

±5%

620

2370

2530

2710

1.1

250

720

2590

2760

2960

1.1

315

880

3270

3470

3730

1.0

400

980

3750

3990

4280

1.0

500

1150

4590

4880

5230

1.0

630

1340

5530

5880

6290

0.85

630

1300

5610 5960 6400 0.85 6.0 800 1520 6550 6960 7460 0.85 1000 1770 7650 8130 8760 0.85 1250 2090 9100 9690 10300 0.85 1600 2450 11000 11700 12500 0.85 2000 3050 13600 14400 15500 0.70 2500 3600 16100 17100 184 00

0.70

1600

2450

1220

12900

13900

0.85

8.0

2000

3050

15000

15900

17100

0.70

2500

3600

17700

18800

20200

0.70

Note: The load losses listed in the table are values for different insulation systems at the reference temperatures in parentheses. Load losses for other insulation systems not included in the table should be converted accordingly based on their respective reference temperatures, using the data for insulation systems at -155℃ (F) as a reference.


Note: Dimensions and weight are subject to change depending on requirements; the data in these two items are based on the manufacturer's specifications.


Data Sheet for 20kV Class 50kVA-2500kVA Unloaded Dry-Type Transformer


Rated Capacity (KVA) Voltage Combination Connection Group Number No-load Loss (W) Load Loss (W) No-load Current (%) Short-circuit Impedance (%)


High Voltage (KV) High Voltage Tap Range Low Voltage (KV) 130℃ (B) (100℃) 155℃ (F) (120℃) 180℃ (H) (145℃)


50 20


22 24 ±2.5%


±5%


0.4 Dyn11


Yyn0 340 1160 1230 1310 2.0 5.0


100 540 1870 1990 2130 1.8


160 670 2350 2470 3460 1.8

200 ±2X2.5%

±5% 730 2770 2940 3140 1.8

250 840 3220 3420 3660 1.8

315 970 3850 4080 4360 1.8

400 1150 4650 4840 5180 1.1

500 1350 5460 5790 6190 1.1

630 1530 6450 6840 7320 1.0

800 1750 7790 8260 8840 1.0

1000 2070 9220 9780 10400 0.85

1250 2380 10800 11500 12300 0.85

1600 2790 13000 13800 14800 0.85

2000 3240 15400 16300 17500 0.70 8.0

2500 3870 18200 19300 20700 0.70

2000 3240 16800 17800 19100 0.70

2500 3870 20000 21200 22700 0.70

Rated Capacity (KVA)

Voltage Combination

Connection Group Number

No-load Loss (W)

Load Loss (W)

No-load Current (%)

Short-circuit Impedance (%)

High Voltage KV) High Voltage Tap Range Low Voltage (KV) 130℃ (B) (100℃) 155℃ (F) (120℃) 180℃ (H) (145℃) 50 20 22 24 ±2.5% ±5% 0.4 Dyn11 Yyn0 340 1160 1230 1310 2.0 5.0 100 540 1870 1990 2130 1.8 160 670 2350 2470 3460 1.8 200 ±2X2.5% ±5% 730 2770 2940 3140 1.8 250 840 3220 3420 3660 1.8 315 970 3850 4080 4360 1.8 400 1150 4650 4840 5180 1.1 500 1350 5460 5790 6190

1.1

630

1530

6450

6840

7320

1.0

800

1750

7790

8260

8840

1.0

1000

2070

9220

9780

10400

0.85

1250

2380

10800

11500

12300

0.85

1600

2790

13000

13800

14800

0.85

2000

3240

15400

16300

17500

0.70

8.0

2500

3870

18200

19300

20700

0.70

2000

3240

16800

17800

19100

0.70

2500

3870

20000

21200

22700

0.70

Data Sheet for 35kV Class 50kVA-2500kVA Unloaded Dry-Type Transformer

Rated Capacity (KVA) Voltage Combination Connection Group No. No-load Loss (W) Load Loss (W) No-load Current (%) Short-circuit Impedance (%)

High Voltage (KV) High Voltage Tap Range Low Voltage (KV) 130℃ (B) (100℃) 155℃ (F) (120℃) 180℃ (H) (145℃)

50 35

36

37

38.5±2.5% 

±5%

0.4Dyn11

Yyn0 450 1340 1420 1520 2.3 6.0

100 630 1970 2090 2230 2.0

160 0.790 2650 2810 3000 1.5

200±2X2.5% 

±5% 0.880 3130 3320 3550 1.5

250 0.990 3580 3800 4060 1.3

315 1170 4250 4510 4820 1.3

400 1370 5100 5410 5790 1.1

500 1520 6270 6650 7110 1.1

630 1860 7250 7690 8230 1.0

800 2160 8600 9120 9760 1.0

1000 2430 9860 10400 11100 0.75

1250 2830 12000 12700 13600 0.75

1600 3240 14600 15400 16500 0.75

2000 3820 17200 18200 19500 0.75

2500 4450 20600 21800 23300 0.75

Rated Capacity (KVA)

Voltage Combination

Connection Group Number

No-load Loss (W)

Load Loss (W)

No-load Current (%)

Short-circuit Impedance (%)

High Voltage (KV)

High Voltage Tap Range

Low Voltage (KV)

130℃ (B) (100℃)

155℃ (F) (120℃)

180℃ (H) (145℃)

50

35

36

37

38.5

±2.5% 

±5%

0.4

Dyn11

Yyn0

450

1340

1420

1520

2.3

6.0

100

630

1970

2090

2230

2.0

160

0.790

2650

2810

3000

1.5

200

±2X2.5% ±5%

0.880

3130

3320

3550

1.5

250

0.990

3580

3800

4060

1.3

315

1170

4250

4510

4820

1.3

400

1370

5100

5410

5790

1.1

500

1520

6270

6650

7110

1.1

630

1860

7250

7690

8230

1.0

800

2160

8 600

9120

9760

1.0

1000

2430

9860

10400

11100

0.75

1250

2830

12000

12700

13600

0.75

1600

3240

14600

15400

16500

0.75

2000

3820

17200

18200

19500

0.75

2500

4450

20600

21800

23300

0.75